9.1.0 - Symptom 1: Unit Will Not Start

 

Cause

 

Remedy

9.1.1

Power off.

1.

Check main disconnect.

9.1.2

Main line open

2.

Check fuses

9.1.3

Loose terminals

3.

Tighten terminals with "POWER OFF"

9.1.4.

Water Flow light not on.

4.

See Section 9.7.1,2,4.

 

 

5.

Failed flow switch. Have switch checked, repair or replace if defective.

9.1.5.

Control circuit open.

6.

Check control voltage fuses and transformer.

       