Automatically Resets When Discharge Pressure Falls To A Safe
Level - Control Located Inside Chiller Unit. |
|
Indoor Air Cooled Condenser |
| Air |
|
|
|
|
|
Cause |
|
Remedy |
|
9.3.1 |
Insufficient condenser air flow |
1. |
Check condenser filter for dirt, fins may be plugged with
dirt or foreign material. |
|
|
|
2. |
Fan belts (if used) may be loose and need adjusting. |
|
|
|
3. |
Check the rotation. |
|
9.3.2. |
Fan motor not operating. |
4. |
Have electrician check fuses and wiring. |
|
|
|
5. |
Have electrician check motor starter and overloads. |
|
|
|
6. |
Have electrician check motor. Repair or replace if defective. |
|
9.3.3. |
Excess refrigerant. |
7. |
Have refrigeration serviceman purge system while operating
until bubbles first appear in sight glass. Then have unit
recharged until glass just clears. |
|
9.3.4. |
Air in system. |
8. |
Have refrigeration serviceman purge the system. |
|
9.3.5. |
Improperly set high pressure control. |
9. |
Have refrigeration serviceman reset or replace the control
if defective. |