9.6.0 - Symptom 6: Unit Shuts Off On Freezestat Control
|
Requires Manual Reset. (Cut Out is
Normally 42° F. For Water Operational)
- Indicated By Red Freezestat Light "On". |
|
|
Cause |
|
Remedy |
|
9.6.1 |
Low water flow |
1. |
Check valves to ensure they are opened. |
|
|
|
2. |
Check if pump is operating. |
|
|
|
3. |
Check and clean filter in the chilled water circuit. |
|
9.6.2 |
Chiller vessel plugged. |
4. |
Call a refrigeration serviceman to inspect the vessel for
foreign material in the chiller inlet or scaling on the tubes. |
|
9.6.3 |
Improperly set freezestat control. |
5. |
Have refrigeration serviceman reset control or replace if
defective |
|
|
|