9.6.0 - Unit Shuts Off On Freezestat Control
Requires Manual Reset. (Cut Out is Normally 42° F. For Water Operational)
- Indicated By Red Freezestat Light "On".
| Cause | Remedy | |
| 9.6.1 | Low water flow | 1. Check valves to ensure they are opened. 2. Check if pump is operating. 3. Check and clean filter in the chilled water circuit. |
| 9.6.2 | Chiller vessel plugged. | 4. Call a refrigeration serviceman to inspect the vessel for foreign material in the chiller inlet or scaling on the tubes. |
| 9.6.3 | Improperly set freezestat control. | 5. Have refrigeration serviceman reset control or replace if defective |