9.6.0 - Symptom 6: Unit Shuts Off On Freezestat Control
|
Requires Manual Reset. (Cut Out is
Normally 42° F. For Water Operational)
- Indicated By Red Freezestat Light "On".
|
|
|
Cause
|
|
Remedy
|
|
9.6.1
|
Low water flow
|
1.
|
Check valves to ensure they are opened.
|
|
|
|
2.
|
Check if pump is operating.
|
|
|
|
3.
|
Check and clean filter in the chilled water circuit.
|
|
9.6.2
|
Chiller vessel plugged.
|
4.
|
Call a refrigeration serviceman to inspect the vessel for
foreign material in the chiller inlet or scaling on the tubes.
|
|
9.6.3
|
Improperly set freezestat control.
|
5.
|
Have refrigeration serviceman reset control or replace if
defective
|
|
|
|