9.8.0 - Cooling Capacity Inadequate
| Cause | Remedy | |
| 9.8.1 | Low refrigerant charge | 1. See section 9.4.1. |
| 9.8.2 | Hot-gas by-pass valve stuck open. | 2. Have repaired or replaced if defective by a refrigeration serviceman. |
| 9.8.3 | Plugged or inoperative T.X. valve. | 3. See section 9.4.2 |
| 9.8.4 | Plugged filter | 4. Check filter in chilled water circuit and clean. |
| 9.8.5 | Inefficient compressor. | 5. See section 9.4.3. |
| 9.8.6 | Air in system. | 6. Purge air, see section 9.3.6. |