Specifications for Film Cooled Chillers


MODEL ACC-5 ACC-10 ACC-15 ACC-25 AC-3.5
LEAVING AIR TEMP
AT DIFFERENT
ENTERING AIR FLOWS
CFM 350 - 40 F 600 - 40 F 1000 - 40F 1600 - 40 F 2400 - 40 F
CFM 470 - 50 F

900 - 50 F

1400 - 50F

2000 - 50 F

2800 - 50 F

CFM 750 - 60 F 1300 - 60 F 1800 - 60 F 2400 - 60 F 2900 - 60 F
REFRIGERATION
CIRCUITS 1 1 1 1 1
NUMBER OF COMPRESSORS - HP 5 10 2 - 7.5 TANDEM 2 - 10 TANDEM 2 - 12.5 TANDEM
NUMBER OF CONDENSER FANS - HP 1/2 1 2 - 1/2 2 - 1 2 - 1
CONDENSER DFM 4000 7790 11,340 16,120 16,120
AIR CONNECTIONS
inches 7 7/8 OD 9 7/8 OD 11 7/8 OD 13 7/8 OD 15 7/8 OD
cm 20 25 30 35 38
CHILLER SIZE
inches 46 x 35 x 75 51 x 39 x 72 88 x 34 x 72 94 x 44 x 78 >120 x 46 x 78
cm 116 x 89 x 190 129 x 99 x 183 223 x 86 x 183 239 x 112 x 198 304 x 116 x 18
CHILLER WEIGHT
lbs 700 840 1430 1580 2000
kg 318 381 650 718 909
KW DRAW
AT 50 FLAT 6.2 12 17.4 23.8 29.0
MIN. CIRCUIT AMPACITY
230/3/60 24 55 64 92 120
460/3/60 12 26/td> 32 36 64
575/3/60 9.6 20 25 29 52
380-415/3/50 12 26; 32 36 72
MAX. DUAL ELEMENT FUSE
208-230/3/60 40 80 80 125 180
460/3/60 20 35 45 50 100
575/3/60 15 25 35 35 80
380-415/3/50 20 35 45 50 110
Capacity based on: 95F (35C) ambient air temperature plus 15 F of blower heat, actual entering air conditions are 105 F (40.5C) dry bulb and and 80 F (26C) wet bulb.
Capacities, Dimensions and Weights are approximate and can change without notice.
50 hertz operation: multiply capacity by 0.83 and kw by 0.85.

1st Choice Portable Chillers, 111 Esna Park Drive, Unit 7, Markham, Ontario, L3R 1H2
Toll Free: 1.877.513.8310 ~ Email: sales@1stchoicechillers.com