<Tower Water Tank Set Specifications

Specifications for Tower Water Tank Sets


MODEL TWPT -25 TWPT - 50 TWPT - 75 TWPT - 100 TWPT - 125 TWPT - 150 TWPT - 200
Capacity Tons 40 70 90 110 135 155 200
TANK SIZE
L x W x H (in) 48 48 48 48 48 60 48 48 72 60 48 72 72 48 72 72 60 72 72 72 72
cm 48 48 48 48 48 60 48 48 72 60 48 72 72 48 72 72 60 72 72 72 72
TANK CAPACITY OPER. LEVEL
Gallons 300 420 540 675 810 1012 1215
Liters 1136 1590 2044 2555 3065 3830 4599
TOWER PUMP FLOW AT 25 PSI
GPM 120 210 270 330 405 465 510
L/s 7.56 13.2 17.0 20.8 25.5 29.3 32.1
PUMP MOTOR HP
3 5 7.5 7.5 10 10 10
PUMP DISCHARGE
in 2.5 2.5 3 3 4 4 4
mm 63.5 63.5 76.2 76.2 101.6 101.6 101.6
PROCESS PUMP FLOW AT 50 PSI
GPM 120 210 270 330 405 465 510
L/s 7.56 13.2 17.0 20.8 25.5 29.3 32.1
PUMP MOTOR HP
7.5 10 15 15 20 20 25
PUMP DISCHARGE
in 2.5 2.5 3 3 4 4 4
mm 63.5 63.5 76.2 76.2 101.6 101.6 101.6
OVERAL SKID DIMENSIONS
L x W x H (in) 90 51 52 90 51 52 90 51 52 90 63 7452 90 75 76 100 75 76 100 75 76
cm 229 130 132 229 130 132 229 130 132 229 160 188 229 190 193 254 190 193 254 190 193
APPROX. SHIPPING WEIGHT
lbs 1900 2050 2300 2500 2900 3550 3950
kgs 863 932 1045 1136 1318 1613 1795
APPROX. OPERATING WEIGHT
lbs 4900 7450 8900 9250 11000 13675 16100
kgs 2227 3386 4045 4205 5000 6216 7319
NAMPLATE AMPS
230 V 26.2 37.5 56.2 56.2 75 75 100
460 V 13.1 18.75 28.1 28.1 37.5 37.5 50
575 V 10.5 15 22.5 22.5 30 30 40
Tower water pump and process flow: 3 gpm/ton.
capacities, Dimensions and Weights are approximate and can change without notice.

STANDARD OPTIONS

  • Automatic chemical treatment packages, automatic backwash sand filters or automatic purge cyclone separators.
  • Three (3) pump manual stand-by tank sets complete with discharge header, isolation valves, chilled and process water pressure and temperature gauges.
  • Four (4) pump automatic standby pump sets complete with discharge headers, automatic starting of standby pumps, chilled and process water pressure and temperature gauges.
  • Sump Pump Systems in two, three and four pump designs. Each complete with foot valves, priming connection with shutoff valve and mounted on a structural steel frame with pump motor starters.
  • Single or double basket strainers or "Y" strainers with isolation valves, low pressure and high temperature alarms.
  • Central control panels with door mounted disconnects, pump fuses, 120V control, run and fail lights, visual or audible alarms.
  • Central thermostats to stage multiple chillers.

1st Choice Portable Chillers, 111 Esna Park Drive, Unit 7, Markham, Ontario, L3R 1H2
Toll Free: 1.877.513.8310 ~ Email: sales@1stchoicechillers.com