1st Choice Chillers
| Products | Trouble Shooting
| Manual | Load
Sizing | Sitemap | Links
| Clients | Components
| Get a Quote
|
|
water chillers
|
| |
|
MODEL
|
WC-3
|
WC-5
|
WC-7.5
|
WC-10
|
WC-15
|
WC-20T
|
WC-25T
|
WC-30T
|
|
CAPACITY
|
|
85 F TOWER WATER,
|
|
LEAVING WATER
|
|
TEMP.
|
|
|
2.75
|
4.5
|
6.7
|
9.45
|
13.5
|
19
|
24
|
27
|
|
|
3
|
5
|
7.4
|
10.9
|
16.5
|
21
|
26
|
33
|
|
|
3.4
|
5.7
|
8.2
|
12
|
18
|
24
|
29
|
36
|
|
REFRIGERATION
|
|
CIRCUITS
|
1
|
1
|
1
|
1
|
1
|
1
|
1
|
1
|
|
NUMBER OF
|
|
COMPRESSORS - HP
|
3
|
5
|
7.5
|
10
|
15
|
2 - 10 TANDEM
|
2 - 13 TANDEM
|
2 - 15 TANDEM
|
|
PUMP - HP
|
3/4
|
1
|
1
|
1 1/2
|
2
|
3
|
3
|
5
|
|
CHILLER FLOW
|
|
gpm
|
7.2
|
12
|
18
|
24
|
36
|
48
|
60
|
72
|
|
m3/hr
|
1.6
|
2.7
|
4.1
|
5.4
|
8.1
|
10.9
|
13.6
|
16
|
|
CHILLER CONNECTIONS
|
|
inches
|
1
|
1 1/4
|
1 1/2
|
1 1/2
|
2
|
2
|
2
|
2 1/2
|
|
mm
|
25.4
|
31.7
|
38.1
|
38.1
|
50.8
|
50.8
|
50.8
|
63.5
|
|
CONDENSER FLOW
|
|
gpm
|
9
|
15
|
22.5
|
30
|
45
|
60
|
75
|
90
|
|
m3/hr
|
2.0
|
3.4
|
5.1
|
6.8
|
10.2
|
13.6
|
17
|
20.4
|
|
CONDENSER CONNECTIONS
|
|
inches
|
1 1/4
|
1 1/2
|
1 1/2
|
1 1/2
|
2
|
2
|
2
|
2 1/2
|
|
mm
|
31.7
|
38.1
|
38.1
|
38.1
|
50.8
|
50.8
|
50.8
|
63.5
|
|
CHILLER SIZE LxWxH
|
|
inches
|
48 x39 x 67
|
48x39 x 67
|
48 x39x 39
|
48 x 39 x67
|
66 x 38 x 70
|
66 x 38 x70
|
66 x 38 x70
|
66 x 38 x 70
|
|
cm
|
122x99x170
|
122x99x170
|
122x99x170
|
122x99x170
|
168x96x178
|
168x96x178
|
168x96x178
|
168x96x178
|
|
CHILLER WEIGHT
|
|
gpm
|
|
kg
|
|
KW DRAW
|
|
AT 50 F L.W.T.
|
2.9
|
4.6
|
6.8
|
9.3
|
14.4
|
18.6
|
22.8
|
28.8
|
|
AT MAXIMUM
|
4.6
|
7.6
|
10.8
|
11.2
|
23
|
22.4
|
36.3
|
46
|
|
MIN. CIRCUIT AMPACITY
|
|
208-220/3/60
|
30
|
48
|
48
|
48
|
48
|
48
|
48
|
48
|
|
230/3/60
|
17
|
27
|
40
|
50
|
75
|
95
|
100
|
140
|
|
460/3/60
|
9.0
|
14
|
20
|
25
|
37
|
47
|
50
|
70
|
|
575/3/60
|
7.0
|
10.5
|
16
|
20
|
30
|
38
|
40
|
56
|
|
380-414/3/50
|
9.0
|
14
|
20
|
25
|
37
|
47
|
50
|
70
|
|
MAX. DUAL ELEMENT FUSE
|
|
208-220/1/60
|
45
|
70
|
70
|
70
|
70
|
70
|
70
|
70
|
|
230/3/60
|
25
|
40
|
60
|
70
|
100
|
130
|
150
|
200
|
|
460/3/60
|
20
|
30
|
30
|
40
|
50
|
70
|
75
|
100
|
|
575/3/60
|
15
|
20
|
25
|
30
|
40
|
50
|
60
|
80
|
|
380-415/3/50
|
20
|
30
|
30
|
40
|
50
|
70
|
75
|
100
|
|
|
Capacity based on: Cooling 2.4 GPM of water from
60F to 50F (15.5C to 10C) with 85 F (29C) entering tower water.
Capacities, Dimensions and Weights are approximate and can change
without notice.
|
|
50 hertz operation: multiply capacity by 0.83 and
kw by 0.85.
|
|
| - |
|
Copyright
© 2008 | 1st Choice Portable Chillers | All rights reserved
|
| |
1st
Choice Portable Chillers, 111 Esna
Park Drive, Unit 7, Markham, Ontario, L3R 1H2
Toll Free: 1,877. 513. 8310 ~ Email: sales@1stchoicechillers.com |